Successfully tested on Fire Doors to comply with AS1905.1
Intumescent retrofit seal for upgrading fire door perimeter gaps where the clearance exceeds the maximum 3mm specified by AS1905.1
- Used to upgrade existing fire doors with up to and including 6mm perimeter gaps
- Can provide up to 2 hours of fire resistance on proprietary fire doors
- Non-compliant fire doors can be salvaged
- Cost-effective solution
- Easy retro-fit installation.
- Ideal for fire engineered solutions where extra protection is necessary for life safety
Specs
Gap Size
Up to and including 6mm fire door side gaps. Please check with your Fire Door manufacturer for the maximum gap allowed
Size
Dimensions: 38mm wide x 1.6mm thick and various lengths
Finish
Standard Colour: White and Silver - Can be painted on-site
Fixing
KG4002 intumescent seal is simply applied to the top and sides of the door frame with two rows of aggressive self-adhesive tape. No screw fixing required
Approvals
Fire:
KG4002 is Fire tested to AS1530.4 for up to 2 hours on proprietary fire door assemblies in accordance with AS1905.1
Please check with your door manufacturer for approvals
By purchasing any product from us, you agree to the following terms of the sale: Before making your purchase, you accept full responsibility for ensuring that the products you are about to purchase have been tested in accordance with relevant Australian standards and building codes such as AS1530 and AS1905 and are compliant to be used on the fire door manufacturer's door type intended to be used, ensuring purchased items do not compromise the selected fire door assembly’s established fire resistance level