Intumescent retrofit seal for upgrading existing nonfire metal frames to fire metal frames specified by AS1905.1
- Allows for a cost-effective and clean build-up of non-rated steel frames with only 15mm stop section, in lieu of the standard 25mm stop section required for fire door frames as per codes and standards
- Allow for Fire Door adjustments in case of reusing any existing Fire Doors and keep in mind the compliance with the existing Fire Door Core manufacturer
- Non-compliant fire door frames can be salvaged
- Easy retro-fit installation
Specs
Dimensions:
1 x (38mm x 1.6mm) and 1 x (13mm x 1.6mm)
Finish
Standard Colour: White and Silver - Can be painted on site
Fixing:
The KG5102 intumescent seal is simply applied to the top and sides of the fire door metal frame with two rows of aggressive self-adhesive tape. No screw fixing required
Gap Size:
Nominal 2mm to 3mm perimeter gaps. Please check with your Fire Door manufacturer for the maximum gap allowed
Approvals
Fire:
Please check with your door manufacturer for approvals
By purchasing any product from us, you agree to the following terms of the sale: Before making your purchase, you accept full responsibility for ensuring that the products you are about to purchase have been tested in accordance with relevant Australian standards and building codes such as AS1530 and AS1905 and are compliant to be used on the fire door manufacturer's door type intended to be used, ensuring purchased items do not compromise the selected fire door assembly’s established fire resistance level
The KG5102 is Fire tested to AS1530.4 for up to 2 hours on proprietary fire door assemblies in accordance with AS1905.1